2100-A4 (Analogue Input Remote Station)


The universal inputs plus outputs gives this station a lot of flexibility. I/O include 4 analogue inputs, 4 digital inputs, 4 relay outputs plus optional 2 analogue outputs.
Field programmable inputs include thermocouples, RTD, Pt100, mA, mV & V, thermister.

Each input can be individually programmed and ranged for any span via on Bd links. The analogue inputs on the 2100-A4 can be expanded up to 64 using the 2100-M input Multiplexers. Outputs include 4 relays for control or alarm, plus an option for 2 analogue outputs of 4~20mA or 0-10V DC.

The 2100-A4 contains 4 in built on/off controllers or alarms. The controller/alarm setpoint (SV) and other parameters are downloaded from the user friendly MicroScan software, Mimic package, and held in permanent memory on the 2100-A4.

Other controller parameters include, output switching differential, auto/manual and manual settings of output. The 4 controllers/alarms on the 2100-A4 will operate unaffected by computer power downs or reboots etc.

The optional 2100-E memory expansion card is designed to allow the 2100-A4 to stand alone, retaining the data collected for intermittent download.

Specifications: (Preliminary)
Analogue Outputs: 4 single ended, 12 bit A/D Each Input can be individually selected on Bd and scaled within the following span limits.
mV: 0~300mV
V: 0~10V
mA: 0~20mA (4~20mA)
RTD (Pt100): -50~850°C (-58~1550°F)
Thermocouple:
K&N:
J:
saas:dss
100~1300°C (212~2400°F)
100~1200°C (212~2200°F)
Thermister:
(10K Beta=3890)
-50~100°C (-58~212°F)
Accuracy: ± 0.1% FSO typical
Digital Inputs: 4 Digital Opto Isolated Inputs
5 to 30V DC
Max Input Frequency: 100 Hz typical on/off and count LED indication on each channel
Relay Outputs: 4 Isolated contact outputs, Change over form C
250V AC. 2amp
30V DC. 2amp
Relay State: Selectable
4 On Board Controllers: On/off action
Communications: Isolated RS422, RS485, RS232
Comms Baud Rate:

19200, 9600, 4800, 2400 selectable
(radio & modem compatable)

Power Supply: 80~265V AC/DC
20~80V AC/DC selectable
8~30V AC/DC optional
Power Supply Consumption 5VA
Expansion Options:
Option 1: Input Expansion. Supports up to four 2100-M input multiplexers. Maximum distance between 2100-A16 & 2100-M = 50m.
Option 2: Two Analogue Outputs: 4~20mA or 0~10V DC
Option 3: Memory Expansion. 2100-E memory expansion card for `stand alone´ monitoring.
Storage capacity = 2000 readings of each input. Options 1 & 2 are not available with this option fitted.

Connections for the 2100-A4

 

Due to on going research and development, designs, specifications, and documentation are subject to change without notification. : No liability will be accepted for errors, omissions or amendments to this specification.