The 2100-D offers
a high degree of flexibility for both the fully isolated
Digital Inputs and Relay Outputs, which are configurable by
the user friendly MicroScan Software.
Configuration of Digital Inputs
include: |
|
(a) |
On/Off state. |
|
(b) |
Flow metering. Pulses from flow or
power meters etc, are accuratly integrated into rate and
totaliser values with virtually no loss of accuracy. |
|
(c) |
Counter function. Pulses are counted
up to 16383 and the counter value reset. |
Relay Outputs include 10 with
change over. Form C contacts, and 2 with normally open Form A
contacts. The output state of the contacts are configurable,
with all settings retained on power down. The 2100-D includes
a communications failure alarm output, and supports
communications via modem or radio.
|
| Specifications: |
| Digital
Outputs: |
12 Isolated Relay
Outputs 10 Change over Form
C 2 Normally Open Form
A 2 A 250V
AC 2 A 30V
DC 0.3A 110V
DC 1/10 H.P. 125V
AC 1/6 H.P. 250V AC |
| Relay
State: |
Software
selectable LED Indication on each
Channel |
| Digital
Inputs: |
12 Digital opto Isolated
Inputs 5 to 30V DC LED Indication
each Channel High Speed Inputs
500 Hz Max |
| Watchdog: |
Built-in Watchdog
Timer Built-in communications
failure alarm |
| Communications: |
Isolated RS422, RS485,
RS232 |
| Comms Baude
Rate: |
19200, 9600, 4800, 2400
selectable Radio and Modem
compatible |
| Power
Supply: |
80~256V
AC/DC 24~80V AC/DC
selectable 8~30V AC/DC
optional Power Supply consumtion
6 VA |
|
|