2100-M (Analogue Input Multiplexer)



The 2100-M is used extensively in industrial plants, with proven reliability and accuracy. It comes complete and ready to operate in a compact DIN rail mount enclosure.

The 2100-M (previously the EXPO-3) can multiplex up to 16 analogue inputs, into one input of a PLC or a Data Logging System. It uses solid state switches, making it extremely reliable and durable.

The 2100-M is widely used to expand up inputs on the 2100-A16 and 2100-A4, plus give economic easy accurate analogue input expansion on a PLC.

The PLC only requires two digital outputs and analogue input to select and recieve data from the 2100-M. For each additional 2100-M added to the system, only one more analogue input is required.
(The typical fan-out for most PLC's is up to eight 2100-M's)

The 2100-M-I, the 2100-M-R and the 2100-M-V are on board input span programmable.
The output can be configured to a selection of industry standard output signals.

Specifications:
Analogue Input Multiplexer:
16 Single ended
Each Multiplexer is span programable with in the specified input type as below:
2100-M-R=RTD Pt100 (-200~600°C) (-330~1100°F)
2100-M-I=4~20 / 0~20mA
2100-M-V=mV & V (-25~500mV and 0~10V DC)
2100-M-T=Thermocouple (-100~1700°C) (-150~3000°F)
Note 1:Minimum Thermocouple span = 200°C (400°F)
Note 2:2100-M-T requires a PI-T transmitter
Accuracy: <± 0.1% FSO Typical
Ambient Drift: < 00.1% / °C FSO Typical
Isolation on clock
& reset:
1kV AC/DC for 1 min
Operating Temperature: 0~60°C
Storage Temperature: -20~80°C
Operating Humidity: 90% RH. Non condensing
Housing: DIN & EN Rail mount
L = 184, W = 127, H=100
Power Supply: 115/230V AC ±  10%. 50/60 Hz
Optional: 24V AC. 50/60 Hz

 

Due to on going research and development, designs, specifications, and documentation are subject to change without notification. : No liability will be accepted for errors, omissions or amendments to this specification.